Air Conditioner Troubleshooting graphic examples

In Electronic Infomation Category: A | on April 15,2011

Example 1: a Lan Boxi Island KC25-type window air conditioner, live shell.

Fault detection: in Figure 1. Measured using the air conditioner 500 V megger between the power plug and CY7C006-35JC datasheet and the ground resistance, the resistance is much less than 2 M.


Figure 1 with megger insulation resistance measurement of the air conditioner shown Figure

Shown in Figure 2. The air conditioner fan motor power plug, again measuring the insulation resistance of air conditioners, measurement results and CY7C006-35JC price and the results of the first measurement no different.


Figure 2 Unplug the fan motor power plug shown Figure

Shown in Figure 3. Air conditioner compressor will disconnect the power plug, then a measurement of air conditioner, insulation resistance, resistance is far greater than 2 M.


Unplug the compressor

Figure 3 Diagram of the power cord

Shown in Figure 4. Insulation resistance measurement of the compressor, the insulation resistance is much less than 2 M, that the compressor insulation deterioration, can no longer be used.


Figure 4 shows the insulation resistance measurement of the compressor map

Shown in Figure 5. Fan motor insulation resistance measurement, resistance is far greater than 2 M, that the fan motor is normal.


Figure 5 shows the insulation resistance measurement of the fan motor diagram

Troubleshooting: replace the same power and CY7C006-35JC suppliers and specification of the compressor.

Example 2: Panasonic CW-172P23H5D a window-type air heat pump device withered in the summer no matter what position selection switch, the fan is not running. The compressor can work properly.

Failure Analysis: Panasonic CW-172P23H5D air conditioner circuit shown in Figure 6. The figure shows, the fan circuit and the selector switch, the fan motor running capacitor (C2), defrost thermostat (26D) is related to the internal fan motor thermal protection switches there. Check this example, the failure should be from several aspects.


Figure 6 Panasonic CW-172P23H5D air conditioner schematic

Will choose low-wind position switch shown in Figure 7. Unplug the fan motor running capacitor (C2) terminal on the wire plug.


Figure 7 unplug the plug on the fan capacitor terminals shown Figure

Fault detection: shown in Figure 8. Two wires were measured with the air conditioner power cord plug end of the turn-on condition L, the measured resistance was 120 and 79 , that selector switch turns on, and the DC resistance of fan motor is also normal.


Figure 8 Measurement of the fan motor and the power plug turn the situation shown Figure

Shown in Figure 9. With a multimeter R 1 k range measuring fan motor capacitor, hands from the beginning of the " " position of the pendulum to the "0 " nearby, and then gradually put the " ", that capacitance is normal.


Figure 9 shows the performance with a multimeter to measure capacitance Figure

Shown in Figure 10. Disconnect the defrost thermostat (26D) plug wire terminals, and measure the defrost thermostat two terminals, found to be not conducting. Such failures are generally due to defrost the outdoor heat exchanger thermostat temperature sensing package or packages connected with the capillary temperature caused a leak. It can be seen from Figure 6, when the defrost thermostat (26D) contacts off, cut off the fan motor power, the fan stops running. Only when the defrost thermostat (26D) contacts are closed, the fan motor operation is possible.


Figure 10 Diagram of measurement of the defrost thermostat

Troubleshooting: replace the defrost thermostat, troubleshooting.